Why do I need surge protection as well as a lightning conductor?
Because most lightning damage is not caused by the strike hitting the building. It arrives as a surge through the incoming electrical supply or along metallic services, from a strike some distance away. The external system protects the structure. Surge protective devices protect what is plugged into it.
What is BS EN 62305-4?
Part 4 of the lightning protection standard covers protection of electrical and electronic systems inside a structure against the lightning electromagnetic impulse. It deals with surge protective device selection and coordination, bonding, screening and zoning, and it is where the requirement for SPDs is set out.
What is the difference between Type 1, 2 and 3 SPDs?
Type 1 devices handle the partial lightning current at the origin of the installation and are used where a structure has an external lightning protection system. Type 2 devices protect distribution boards from residual surges. Type 3 devices sit close to sensitive equipment as a final stage. They work as a coordinated set, not as alternatives.
Can my electrician fit the SPDs?
Yes. Surge protective devices inside the building are installed under BS 7671 and a competent electrical contractor can fit them. What the electrician usually does not have is the BS EN 62305-2 risk assessment that says which devices are needed and where, and the coordination with the external system. We provide that part.